Double Tank Transformer
Double Tank Transformer
The transformer with double tank by its electrical characteristics corresponds to ECO-DESIGN according to European
directive 2009/125/EC, Regulation (EU) n0 548/2014. In case of leakage or explosion of the internal tank, the external
tank is capable of capturing the complete amount of the transformer oil.
The technical characteristics listed below can be adjusted to the particular customer’s needs.
Technical characteristics of GTED-100.20,5:
Rated Power (kVA): 100
Rated Voltage (kV): 10; 20.5/0.410
Highest voltage level of equipment (kV): 24
Connection: Dyn 11
No-load losses (W): 145 (A0)
Load loses (W): 1750 (CK)
Impedance voltage (%): 4
Cooling: ONAN
Temperature class: A
Frequency (Hz): 50
Standard: IEC 60076-1
Double tank design:
In case of leakage in the internal tank, the external tank captures all the leaking oil.
Download pdf brochure for Double Tank Transformer